| Charateristics according to DIN EN 13501-2 | Definition/
classifikation | Achieved protection targets withhin the fire resistance classes | Approvals (tests acccording to DIN EN 1363- 1 and DIN EN 1364-1 and DIN EN 14600 durability and functional test) |
 | E | Integrity is the resistance against fire to avoid a passage of flames or hot gases. (The protection target EI is achieved by fire load free zone EI 30 = 1,0 m, EI 60 = 1,5 m, EI 90 = 2,0 m.) Protection target EI 30: x = 1000 mm Protection target EI 90: x = 2000 mm | E 90 E 120 E 240 | UB III/B-06-005 UB III/B-07-010-1 UB III/B-05-020 UB III/B-06-016 GU IV/97-73 UU IV/97-25 UB III/B-04-045 LP-1216.2/02 UB III/B-08-033 3344/097/09 UB 3.1 / 09-018 UB 3.1 / 09-021 UB 3.3 / 09-020 IBS 08062416 UB 3.3 / 10-018-1 UL 10D for E120 UL 10P for E120 UL 10C for E120 |
 | EW | Integrity with a limitation of heat transmission Limitation of the heat transmission is the characteristic to reduce heat transferred through a fire protection system to limiting materials. (The protection target EI is achieved by fire load free zone). Protection target EI 30: x = 200 mm Protection target EI 60: x = 300 mm Protection target EI 90: x = 500 mm | EW 30
EW 60
EW 90
EW 120 | UB III/B-08-012 UB III/B-07-003 UB 3.3/ 10-035-1 UB 3.3/ 11-009-1 |
 | E+ Sprinkler | Insulation with intensified sprinkler protection Insulation is the ability of the system to avoid the transmission of fire caused by heat transmission. The transmission has to be limited in a way, that neither the opposite fire side surface nor any materials near to this surface may ignite an so persons are protected.
x = 200 - 500 mm depending on the environment | EI 90 EI 120 EI 180 | UB III/B-08-016 UB III/B-05-006 IBS 08062415 UB III/B-07-10-2 |
 | E+ Water film | In case of fire - heat insulation with a water film (The surface temperature is lower than the admissible limit value) | EI 90 EI 120
EI 180 | 08/32309876 Part 1 2011-Efectis-R0495
|
 | EI dry | Insulation without water in case of fire | EI30
EI 60 | (3162/794/10)-AH (3699/959/10)-AH 304/878/09 3053/504/10
|
 | Transmission from one floor to another | Avoidance of transmission of flames from one level to another without (with) balustrade | The necessary barrier (or lintel) of 1 m height is automatically created in case of fire. | B 15045 UB III/B-05-006-A1 proof of weathering
|
 | Extinguishing | Creation of sections
Limitation of a room which is usually not there to avoid the transmission of flames or hot gases to the room without fire. Enclosure by textile fire protection closures with the targets: limitation of the fire, smothering of the fire, extinguishing of the fire by gases or water-spray. | Enclosure by textile fire protection closures with the target to: - limit the fire
- quench the fire
- extinguish the fire with gases or water-spray
|