Type Fiberseal-H

Fiberseal-H



The (H)orizontal smoke protection closure for openings in the ceiling




Characteristics of the Fiberseal-H


  • tested according to DIN EN 1643-3 resp. DIN 18095-3 with classification according to DIN EN 13501-2 of class Sa – max. leakage of 3 m³/h per meter at ambient temperature and 20 Pa
  • for large ceiling openings as smoke protection closure up to 20 m width and a drop length up to 8 m in the class Sa DIN EN 13501-2
  • ceiling openings of the Sm class
  • tested for 1.000 cycles
  • secure closing of the duplex-drive system with secured power supply
  • active sealing system for compressed-air technologies
  • high-quality fabric with silicone coating, optional PU coating
  • installation flexibility under the ceiling or in ceiling openings
  • tension cables at a distance of 1.5 m to support the tissue at large dimensions, as well as for pressure loads during a fire

Dimension table (standard version)

Clear widthDrop lengtha
(mm)
b
(mm)
t
(mm)
h
(mm)
< 20 m< 8 m270355350
270

 
Clear width (CW)   Clear height (CH)



Choice of casings


 
Fixed bearing   Floated bearing



Receiving box and bottom bar





Side guide





Installation options


Installation under the ceiling Installation in the ceiling opening



Protection targets


Protection target No requirements for fire protection closure Requirements E 120
(Integrity)
Tested according to DIN EN 1634-3
Characteristics according to DIN EN 13501-2
  Demand E (Integrity)
Demand E (Integrity)
Fabric Protex 1100 2S
Fabric
Protex 1100 2S
Certification of the permanent function according to DIN EN 14600 class C1 = 500 cycles
test report MPA 1,3 m³/h per linear meters length of joint
Certification of the permanent function according to DIN EN 14600 class C1 = 500 cycles
Smoke protection closure: test report MPA 1,3 m³/h per linear meters length of joint
Fire protection closure:
UB III/B-05-020 (E 120)
Max. dimensions (w x h) technically feasible
20 m x 8 m
Max. dimensions (w x h) technically feasible
20 m x 8 m


*) Limitations through country-specific extrapolations are possible