Type Fiberseal-Sa

Fiberseal-Sa



The tight smoke protection closure with the classification (Sa) tested for large openings




Characteristics of the Fiberseal Evoultion-Sa


  • tested according to DIN EN 1643-3 resp. DIN 18095-3 with classification according to DIN EN 13501-2 of class Sa – max. leakage of 3 m³/h per meter at ambient temperature and 20 Pa
  • max. approved dimensions according to the AbP 10 m x 6 m (for EW90 requirements 10 m x 5 m)
  • cycle test according to class C2 = 10.000 cycles
  • versatile mounting options
  • passive sealing system for closing, so that no compressors and wear parts are necessary. By this also the possibility of using it as a fire protection closure is given, as no sealing parts are combustible
  • additional protection targets by special fabrics for fire resistance classes of E 120 and also up to EW90
  • high quality fabric with silicone coating, optionally with PU coating
  • patented tubular motor drive system with Gravigen technology
  • integrated safety edge as an option


Fabric System width Drop length t
(mm)
h
(mm)
Fabric
Protex 600 S / Ecotex 1100 2S < 10 m ≤ 6 m 350
260 Standard
Protex 600 S / Ecotex 1100 2S < 5 m ≤ 4,5 m 285
200 Special
Protex 600 S / Ecotex 1100 2S < 3,5 m ≤ 3,5 m 190
290
Special
Protex 600 S / Ecotex 1100 2S < 7 m ≤ 5 m 290
360
Special
Heliotex < 7 m ≤ 3,5 m 350
260 Standard
Heliotex< 5 m ≤ 2,5 m 285 200
Special
Heliotex < 3,5 m ≤ 2 m 190
290
Special
Heliotex < 6 m ≤ 3 m 290
360 Special

Casing 285 x 200 only for ceiling mounting

 

 

Standard casing         Special casing



Casing


Standard casing   Special casing   Special casing for self-levelling bottom bar
Standard casing   Special casing   Special casing for self-levelling bottom bar



Bottom bars


       
Type 4,6   Heavy, Type 9,6   Small, Type 5,61   Type 3,84 F Self-levelling bottom bar without safety edge   Typ 3,84 FK Self-levelling, bottom bar



Choice of side guides


Installation to the wall   Installation in the embrasure   Installation in the niche
Installation to the wall   Installation in the embrasure   Installation in the niche



Installation options


Installation of the casing to the wall   Installation of the casing to the wall, 
false ceiling is unilaterally connected to the casing   Installation of the casing directly to the ceiling
Installation of the casing to the wall   Installation of the casing to the wall, false ceiling is unilaterally connected to the casing   Installation of the casing directly to the ceiling

Installation of the casing directly to the ceiling, false ceiling is connected to the casing on both sides   Installation of the casing over a suspension to the ceiling   Installation of the casing over a suspension to the ceiling
false ceiling is connected to the casing on both sides, without fire protection
Installation of the casing directly to the ceiling, false ceiling is connected to the casing on both sides   Installation of the casing over a suspension to the ceiling   Installation of the casing over a suspension to the ceiling false ceiling is connected to the casing on both sides, without fire protection



Protection targets


Smoke protection closure tested according to DIN EN 1634-1/3, classified according to DIN EN 13501-2

Protection target No requirements for fire protection Requirement up to E 120
(integrity)
Requirement up to EW 90
(radiation protection)
Requirement up to EI 120
(characteristic: heat insulation/with water)
Sa
tested according to
DIN EN 1634-3

  Requirement up to E 120 (integrity) Requirement up to EW 90 (radiation protection) Requirement up to EI 120 (characteristic: heat insulation/with water)
Protection target Sa

Max. dimensions according to AbP

limitated by the standard
(w x h)

10 m x 6 m

Max. dimensions according to test
report
(w x h)

10 m x 6 m *

Max. dimensions according to test
report
(w x h)

10 m x 6 m *

Max. dimensions according to test
report
(w x h)

10 m x 6 m *
Fabric Protex 600 S Fabric Ecotex
1100 2S
Fabric

Ecotex 1100 2S
1) Heliotex

Fabric Ecotex 1100 2S
Certificate AbP:
P-3359/
128/08
MPA Braun­schweig
Certificate Test reports:
P-3286-0926
MPA Braun­schweig,
UB III/B-06-15
(E 120)
Certificate Test reports
P-3286-0926
MPA Braun­schweig,
UB III/B-08-012
(EW 90)
UB III/B-06-15
(EW 30)
Certificate

Test reports
P-3286-0926
MPA Braun­schweig,
UB III/B-08-016 (EI 120)

 *) Limitations through country-specific extrapolations are possible.