The tight smoke protection closure with the classification (Sa) tested for large openings
Characteristics of the Fiberseal Evoultion-Sa
- tested according to DIN EN 1643-3 resp. DIN 18095-3 with classification according to DIN EN 13501-2 of class Sa – max. leakage of 3 m³/h per meter at ambient temperature and 20 Pa
- max. approved dimensions according to the AbP 10 m x 6 m (for EW90 requirements 10 m x 5 m)
- cycle test according to class C2 = 10.000 cycles
- versatile mounting options
- passive sealing system for closing, so that no compressors and wear parts are necessary. By this also the possibility of using it as a fire protection closure is given, as no sealing parts are combustible
- additional protection targets by special fabrics for fire resistance classes of E 120 and also up to EW90
- high quality fabric with silicone coating, optionally with PU coating
- patented tubular motor drive system with Gravigen technology
- integrated safety edge as an option
Fabric |
System width |
Drop length |
t (mm) |
h (mm) |
Fabric |
Protex 600 S / Ecotex 1100 2S |
< 10 m |
≤ 6 m |
350
|
260 |
Standard |
Protex 600 S / Ecotex 1100 2S |
< 5 m |
≤ 4,5 m |
285
|
200 |
Special |
Protex 600 S / Ecotex 1100 2S |
< 3,5 m |
≤ 3,5 m |
190
|
290
|
Special |
Protex 600 S / Ecotex 1100 2S |
< 7 m |
≤ 5 m |
290
|
360
|
Special |
Heliotex |
< 7 m |
≤ 3,5 m |
350
|
260 |
Standard |
Heliotex | < 5 m |
≤ 2,5 m |
285 |
200
|
Special |
Heliotex |
< 3,5 m |
≤ 2 m |
190
|
290
|
Special |
Heliotex |
< 6 m |
≤ 3 m |
290
|
360 |
Special |
Casing 285 x 200 only for ceiling mounting
|
 |
|
|
 |
Standard casing Special casing
|
Casing
|
|
|
|
|
Standard casing
|
|
Special casing
|
|
Special casing for self-levelling bottom bar
|
Bottom bars
|
|
|
|
|
|
|
|
|
Type 4,6
|
|
Heavy, Type 9,6
|
|
Small, Type 5,61
|
|
Type 3,84 F
Self-levelling bottom bar without safety edge
|
|
Typ 3,84 FK
Self-levelling, bottom bar
|
Choice of side guides
|
|
|
|
|
Installation to the wall
|
|
Installation in the embrasure
|
|
Installation in the niche
|
Installation options
|
|
|
|
|
Installation of the casing to the wall
|
|
Installation of the casing to the wall,
false ceiling is unilaterally connected to the casing
|
|
Installation of the casing directly to the ceiling
|
|
|
|
|
|
Installation of the casing directly to the ceiling, false ceiling is connected to the casing on both sides
|
|
Installation of the casing over a suspension to the ceiling
|
|
Installation of the casing over a suspension to the ceiling
false ceiling is connected to the casing on both sides, without fire protection
|
Protection targets
Smoke protection closure tested according to DIN EN 1634-1/3, classified according to DIN EN 13501-2
Protection target |
No requirements for fire protection |
Requirement up to E 120 (integrity) |
Requirement up to EW 90 (radiation protection) |
Requirement up to EI 120 (characteristic: heat insulation/with water) |
Sa tested according to DIN
EN 1634-3
|
|
 |
 |
 |
 |
Max. dimensions according to AbP limitated by the standard (w x h) |
10 m x 6 m |
Max. dimensions according to test report (w x h) |
10 m x 6 m * |
Max. dimensions according to test report (w x h) |
10 m x 6 m * |
Max. dimensions according to test report (w x h) |
10 m x 6 m * |
Fabric |
Protex 600 S |
Fabric |
Ecotex 1100 2S |
Fabric |
Ecotex 1100 2S 1) Heliotex |
Fabric |
Ecotex 1100 2S |
Certificate |
AbP: P-3359/ 128/08 MPA Braunschweig |
Certificate |
Test reports: P-3286-0926 MPA Braunschweig, UB III/B-06-15 (E 120) |
Certificate |
Test reports P-3286-0926 MPA Braunschweig, UB III/B-08-012 (EW 90) UB III/B-06-15 (EW 30) |
Certificate |
Test reports P-3286-0926 MPA Braunschweig, UB III/B-08-016 (EI 120) |
*) Limitations through country-specific extrapolations are possible.
|
|
 |
|
|
|