Automatic curved smoke curtain - Smokeshield-C type

Smokeshield-C


The curved smoke curtain with a leakage of 0%

 

 
 



System description


Smokeshield-C
  • The flexible smoke curtain with a closed, curved course is designed for an installation in circle- or ellipse-shape but also as an open, curved (serpentine) smoke curtain
  • For the time and temperature-class D 60 resp. D 120 (600°C)
  • Since the smoke curtains consists of one fabric panel there is no overlapping and no remaining openings
  • Integrated in the suspended ceilings
  • Connection to the ceiling panel with laser-cut bottom rail over self-levelling bearing elements
  • Alternatively with direct connection to the false ceiling (hardly visible, only 2mm mismatch) or by a shadow groove execution
  • As standard the smoke curtain closes by the engine system gravigen, that means closing without auxiliary energy, hence no fire- resistant cables are needed
  • Extreme widths of the smoke curtain up to 300 m and drop length up to 4m (for curve shape radii > 4m)
  • The textile surfaces are piled stored on the completion modul under the ceiling
  • Connected completion modul over the total length of the smoke curtain
  • Optional: integrable ligthings in the completion modul


Dimensions


   
  Bottom
bar in shadow groove
execution
  Bottom
bar with direct connection to the ceiling

   
   

Drop length
A
Installation height
E
0,1 - 1,5 m
560 mm
1,5 - 3,0 m 700 mm
3,0 - 4,0 m 800 m

 

 



Previous solution:

Devided, overlapping smoke curtain elements

STÖBICH´s INOVATION:

Continous smoke curtain
<br><br> <br><br>







Range of curve courses







CE-Classification




Patented tubular motor with Gravity Fail Safe technology
 


 

Modutex 600 A2
 
 
Kennzeichnung
EN 12101-1
Stöbich
System Smokeshield-C
Automatic smoke curtainTyp ASB 1 / ASB 3
Closing without electric energy
Temperature classificationD120
(600°C / 120 min)
Closing Time
(depending on the drive)
0,12 m/s
e.g. drop length 4 m = 30 s in fire alarm position
Gap - casing0 mm
Gap edges embrasure0 mm
Gap joint0 mm
Max. permeability of the smoke
curtain fabric with ambient
temperature and 200 °C
(max. 25 m³/m²/h)
< 1m3/m2/h
Free area casing= Casing length x gap casing
= L x 0 = 0 mm2
Free area casing= D x gap edges
Free area edges= D x gap joint x number of joints
CE-Certificate of Conformity
Applied
Building approval for the fire behaviour
of the fabric
D 120
Z - 56. 429 - 91
D = drop length of the smoke curtain
 
Joint
 

Casing
 

Edges